Rated Current – 80 Amps
Provides reliable protection for circuits with medium-to-high power demand in commercial and industrial applications.
Three-Pole (3P) Configuration
Ideal for three-phase systems, ensuring comprehensive protection across all phases of the circuit.
C-Type Tripping Curve
Trips between 5 to 10 times the rated current. Suitable for installations where inrush currents occur, such as with motors, compressors, and fluorescent lighting.
6kA Short Circuit Breaking Capacity
Can safely interrupt fault currents up to 6,000 Amps, preventing damage to connected equipment and minimizing fire risk during faults.
DIN Rail Mountable
Quick and standardized DIN rail installation (35mm) for easy integration into any modern distribution board or panel.
FEATURES:
Flame-Retardant Casing
Constructed from self-extinguishing thermoplastic material, ensuring fire safety even in overload conditions.
Wide Temperature Range
Operates efficiently in environments ranging from -25°C to +70°C, suitable for diverse installation conditions.
Mechanical & Electrical Durability
High endurance with 20,000 mechanical operations and 4,000 electrical operations, guaranteeing long-term performance.
Clear ON/OFF Manual Toggle
Provides intuitive operation and status visibility. Includes trip indication for easy fault identification.
Terminal Flexibility
Compatible with rigid (1.0 – 25 mm²) and flexible (1.0 – 16 mm²) conductors for versatile wiring options.
Attribute |
Specification |
Rated Current (In) |
80 Amps |
Number of Poles |
3 (Three-Phase) |
Tripping Characteristic |
C-Type (5–10x rated current) |
Breaking Capacity (Icn) |
6,000 Amps (6kA) |
Operating Voltage (Un) |
415V AC |
Frequency |
50/60 Hz |
Mounting |
DIN Rail (35mm) |
Compliant Standards |
IEC 60898-1, IEC 60947-2 |
Operating Temperature Range |
-25°C to +70°C |
Mechanical Endurance |
≥ 20,000 operations |
0 Reviews For this Product